Product overview
A third stage power surge protector, suitable for installation in various types of power supply distribution box terminal, and the other junction between LPZ2 and PLZ3 zones and subsequent partition of the region.
Main characteristics
Module self-locking function to avoid the loss of protection because of loose;
Plug-in modules for easy replacement.
Technical data
Rated operating voltage Un | 220VAC | 220VAC | 220VAC |
Maximum operating voltage Uc | 385VAC | 385VAC | 385VAC |
Nominal discharge current In (8 / 20μs) | 10KA | 10KA | 10KA |
The maximum discharge current (8 / 20μs) | 20kA | 20kA | 20kA |
Protection voltage Up ( under In) | <1200V | <1200V | <1200V |
Cross-sectional area of connecting wire | 1.5mm²~25mm² Flexible wire | 1.5mm²~25mm² Flexible wire | 1.5mm²~25mm² Flexible wire |
Response time | <25ns | <25ns | <25ns |
Leakage current | <10μA | <10μA | <10μA |
Degrees of protection provided by enclosure (in line with IEC 60529) | IP 20 | IP 20 | IP 20 |
Housing material/flammability rating | UL94-V0 | UL94-V0 | UL94-V0 |
Test standard | GB 18802.1/IEC 61643-1 | GB 18802.1/IEC 61643-1 | GB 18802.1/IEC 61643-1 |
Applied power system | Single phase two wire | Three-phase four-wire(TN-C system) Three-phase three-wire(IT system) |
Three-phase five-wire(TN-S system) |
Aging indicator function | Yes(Indicator window turnsfrom green to red) | Yes(Indicator window turns from green to red) | Yes(Indicator window turns from green to red) |
Fuse or circuit breaker selection(A) | 25、32 | 25、32 | 25、32 |
Aging thermal separation function | yes | yes | yes |
Working temperature range -40 | -40~+80℃ | -40~+80℃ | -40~+80℃ |
Installation method | DIN35mm rail | DIN35mm rail | DIN35mm rail |
Diagram
Schematic diagram
Dimension drawings