PHL-TA-20/385/4P

AC Power SPD(20kA)

Request a Quote

PRODUCTS DETAILS

Product overview

A third stage power surge protector, suitable for installation in various types of power supply distribution box terminal, and the other junction between LPZ2 and PLZ3 zones and subsequent partition of the region.

Main characteristics

Module self-locking function to avoid the loss of protection because of loose;

Plug-in modules for easy replacement.

Technical data

Rated operating voltage Un 220VAC 220VAC 220VAC
Maximum operating voltage Uc 385VAC 385VAC 385VAC
Nominal discharge current In (8 / 20μs) 10KA 10KA 10KA
The maximum discharge current (8 / 20μs) 20kA 20kA 20kA
Protection voltage Up ( under In) 1200V 1200V 1200V
Cross-sectional area of connecting wire 1.5mm²~25mm² Flexible wire 1.5mm²~25mm² Flexible wire 1.5mm²~25mm² Flexible wire
Response time 25ns 25ns 25ns
Leakage current 10μA 10μA 10μA
Degrees of protection provided by enclosure (in line with IEC 60529) IP 20 IP 20 IP 20
Housing material/flammability rating UL94-V0 UL94-V0 UL94-V0
Test standard GB 18802.1/IEC 61643-1 GB 18802.1/IEC 61643-1 GB 18802.1/IEC 61643-1
Applied power system Single phase two wire Three-phase four-wire(TN-C system)
Three-phase three-wire(IT system)
Three-phase five-wire(TN-S system)
Aging indicator function Yes(Indicator window turnsfrom green to red) Yes(Indicator window turns from green to red) Yes(Indicator window turns from green to red)
Fuse or circuit breaker selection(A) 2532 2532 2532
Aging thermal separation function yes yes yes
Working temperature range -40 -40~+80 -40~+80 -40~+80
Installation method DIN35mm rail DIN35mm rail DIN35mm rail

 

Diagram

PHL-TA-20 385  2P.png

Schematic diagram

PHL-TA-20 385  2P-1.png

Dimension drawings

PHL-TA-20 385  2P-2.png

Contact us

Please feel free to give your inquiry in the form below We will reply you in 24 hours

Leave YourMessage

Thank you! We will reply you via email within 24 hours.