PHG-11TF-28

Digital Input Signal Isolator 
PHG-11TF-28 1 input and 1 output

Input: Switch contacts/proximity switches
Output: Transistor

Request a Quote

PRODUCTS DETAILS

Overview

The switching input transistor output signal isolator converts the input signal of the switch contact or proximity switch into a transistor output through isolation. Line faults are detected via a separate relay output (optional) and displayed via LED lights on the top of the module. The switch of the module is used to select the phase of the channel and whether the line fault detection function is required.
This product needs to be powered independently, and the power supply, input and output terminals are isolated.

Specifications

Input
Input signal Switch contacts/proximity switches
The supply voltage of the sensor About 8V
Input frequency range ≤5kHz
Input/output characteristics:
On site input current >2.1mA, the output is closed, indicating ON;
When<1.2mA, the output is open circuit, indicating OFF
Output normally open/normally closed state switch control When the dial switch K1 is at "ON", the transistor output e-c are in inverted phase
When the dial switch K1 is at "OFF", the transistor output e-c are in normal phase
When the K2 is at  "ON", the circut will select the red light LFD indication alarm function
Output
Output signal Transistor, alarm relay (optional)
Output characteristic NPN type transistor emitter or collector open circuit output
Drive capability Output current ≤ 20mA (1.2k Ω), maximum internal current 100mA, equipped with short-circuit current protection
Basic parameters
Supply voltage 20~35VDC
Power consumption <1W(24V power supply, when the transistor is conducting)
LED indicator Green: Power indicator
Yellow: Output transistor in normal working state
Red: LFD indication, line fault alarm
Temperature parameters Working temperature: -20℃ ~ +60℃,
Storage temperature: -40℃ ~ +80℃
Relative humidity 10%~95% RH no condensation
Insulation strength ≥2000VAC/min(between input/output/power supply)
Insulation resistance 100MΩ (500 VDC) (between input/output/power supply)
Electromagnetic compatibility GB/T 18268(IEC 61326-3-1)
MTBF 800000h
Wire requirements Horizontal cutting surface ≥ 0.5mm2; Insulation strength ≥ 500V
Applicable field equipments Field equipment such as dry contacts or NAMUR type proximity switch inputs that comply with DIN19234 standard

 

Dimension

PHG-11TF-28.jpg

Connection wiring

PHG-11TF-28(1).jpg

Note: 
1. The power supply of the power rail is an optional function. Users need to specify the power supply mode when ordering. Please refer to attachment on page 89.

PHG-11TF-28(2).jpg

Line Fault Detection

Users can select the "ON" side of the switch at the top of the module to enable fault detection function and indicate an alarm through the red LED light. On site input current>7mA, short circuit alarm (SC); On site input current<0.1mA, open circuit alarm (LB). If the switch contact input requires fault detection function (wire breakage, short circuit), a 22k Ω resistor should be connected in parallel at both ends of the switch, and a 680 Ω resistor should be connected in series (as shown in the wiring diagram for switch contact II).