PHG-11TE+/PHG-12TE+

Surge Protection Type Analogue Input Signal Isolators
PHG-11TE+   1 input and 1 output
PHG-12TE+ 1 input and 2 outputs

Input: two or three-wire transmitter or current source signal
Output: DC signal (current/voltage)

Request a Quote

PRODUCTS DETAILS

Overview

The surge protection analog input signal isolator can convert two- or three-wire 4~20A or current source signals into current or voltage signal output through the isolator. The output parameters can be customized according to user needs.
This product needs to be powered independently, and the power supply, input and output terminals are isolated.

Specifications

Input
Input signal Two or three-wire transmitter or current source signal
Distribution voltage  ≥18V
Input impedance ≤100Ω
Output
Output signal DC signal (current/voltage)
Load resistance Current load resistance ≤500Ω
Voltage load resistance <5mA
Surge protection features:  
Nominal discharge current ln(8/20μs) 5kA
Voltage protection level Up(8/20μs): 60V(line to line)
Voltage protection level Up(8/20μs): 600V(line to ground)
According to standards GB/T18802.21-2016(equivalent to 1EC61643-21:2012)
Basic parameters
Supply voltage 20~35VDC
Power consumption Current output <1.3W; voltage output <1W (PHG-11TE+ series)
Current output <1.8W; voltage output <1W (PHG-12TE+ series)
LED indicator Green: power indicator
Response time 5ms to reach 90% of the final value
Temperature drift 0.005% F.S/℃
Temperature parameters Working temperature: -20℃ ~ +60℃,
Storage temperature: -40℃ ~ +80℃
Relative humidity 10%~95% RH no condensation
Insulation strength ≥2000VAC/min (between input/output/power supply)
Insulation resistance 100MΩ (500 V DC) (between input/output/power supply)
Electromagnetic compatibility GB/T 18268,IEC 61326-1
MTBF 80000h
Wire requirements Horizontal cutting surface ≥ 0.5mm2; Insulation strength ≥ 500W
Applicable field equipments Two, three-wire (HART) transmitter or current source

Dimension

PHG-11TE+.jpg

Connection wiring

PHG-11TE+(1).jpg

Note: 
1. PHG-11TE+ does not include output 2 part. 
2. The power supply of the power rail is an optional function. Users need to specify the power supply mode when ordering. Please refer to attachment on page 89.

Specifications, models and codes

PHG-11TE+(3).jpg

For example: one input and one output, two or three wire 4~20mA input, 4~20mA output, 24V power supply, model: PHG-11TE-21+

Contact us

Please feel free to give your inquiry in the form below We will reply you in 24 hours

Leave YourMessage

Thank you! We will reply you via email within 24 hours.

return