PHD-22TZ-*1*1

RTD input isolated safety barrier

RTD input/ 4~20mA output (configurable)
2 inputs 2 outputs

Request a Quote

PRODUCTS DETAILS

Overview

The RTD input isolation safety barrier can convert the two wire or three wire thermistor (RTD) signals in hazardous areas into 4-20mA current signals and output them to the safety zone. It can be intelligently configured, and the actual range of the thermal resistance can be set through computer software. It has the functions of wire breakage alarm and out of range alarm.

This product requires independent power supply, with isolated power supply, input, and output terminals.

"*" represents the input type of the thermistor, and the specific model is represented by a code (see "Input Signal Type and Range Table" for details).

 

Input signal types and measurement range

Code RTD model Measurement range Minimum range Conversion accuracy
1 G53 -50~150℃ 20℃ 0.2℃/0.1%
2 Cu50 -50~150℃ 20℃ 0.2℃/0.1%
4 Pt100 -200~850℃ 20℃ 0.2℃/0.1%
6 Pt1000 -200~850℃ 20℃ 0.2℃/0.1%
7 Ni1000 -60~250℃ 20℃ 0.2℃/0.1%

Example: Isolated safety barrier Pt100 input, temperature range 0~400℃, two outputs are with 4~20mA, the power supply is 20~35VDC. The model is PHD-22TZ-4141(0~400℃), the measurement range can be set to the specified range of 0~400℃ by computer.

* Bus terminal power supply, please see appendix for details.

 

Specifications

 

Input in harzadous area

 

Input signal

Two wire or three wire thermistor signals (see "Input Signal Type and Range Table" for details)

Input disconnection

The default "low alarm" can be modified to "high alarm" through configuration software

Signal range

Corresponding measurement range of thermal resistance

Measurement range

Users make their own configuration when ordering, and indicate it at the tail number or otherwise.

Safety side output:

 

Output signal

4~20mA

Output load capacity

0~500Ω(customizable)
Optional voltage output type, load resistance RL ≥ 330kΩ

Supply Voltage

20-35VDC

Power consumption

≤ 90mA ( when 24VDC power supply,  20mA output)

LED indicator

Green: Power indicator
Yellow: Signal transmission from safety zone to danger zone
Red: Signal transmission from danger zone to safety zone

Output accuracy

Please refer to the "Input Signal Type and Range Table" for details

Response time

Reaching 90% of the final value within 300ms

Temperature drift

0.005%F.S/℃

Temperature parameters

Working temperature: -20℃~+60℃
storage temperature:-40℃~+80℃

Relative humidity

10%~95% RH no condensation

Dielectric strength

Between intrinsically safe side and non-intrinsically safe side (≥ 3000VAC/min);
between power supply and non-intrinsically safe terminal (≥ 1500VAC/min)

Insulation resistance

≥100MΩ (between input/output/power supply)

Electromagnetic compatibility

According to IEC 61326-1(GB/T 18268), IEC 61326-3-1

MTBF

100000h

Wire requirements

Horizontal cutting surface ≥ 0.5mm2; Insulation strength ≥ 500V

Applicable field equipments

Two wire or three wire thermistors
G53, Cu50, Pt100, Pt1000, Ni1000

Installation place

Installed in a safe zone, it can be connected to intrinsic safety instruments in hazardous areas up to Zone 0, IIC, Zone 20, and IIIC

Intrinsically safe certification

 

Functional safety certification

SIL3 according to IEC 61508 standards

Explosion proof mark

[Ex ia Ga]lIC [Ex ia Da]lllC

Explosion-proof standard

GB/T3836.1-2021  GB/T3836.4-2021

Terminals 1-3、2-3、4-6、5-6

Um:250V AC/DC Uo=8.4V DC lo=31mA
Po=65.1mW Co=4.8μF Lo=20mH

Certification body

CQST(China National Quality Supervision and Test Centre for Explosion Protected Electrical Products)

 

Schematic diagram

Note:

  1. The power rail function is an optional function, and users need to specify the power supply method when placing an order
  2. The selection of power rail connectors can refer to page 89 of the "Annex"
  3. When inputting a three wire RTD, it is necessary to ensure that the three wires are of equal length as much as possible
  4. When inputting a two-wire RTD, safety barrier terminals 4 and 2 must be short circuited

 

Terminal assignments and dimensions

Terminal

Terminal assignments

14

Power supply+

20~35VDC

15

Power supply-

 

2-wire

3-wire

4

Input 1+

Input 1+

5

Input 1-

Input 1-

6

with 5 short connected

Input 1-

1

Input 2+

Input 2+

2

Input 2-

Input 2-

3

with 2 short connected

Input 2-

8

Output 1+

4~20mA

9

Output 1-

11

Output 2+

4~20mA

12

Output 2-

 

Contact us