Overview
The frequency signal is input into the isolated safety barrier, which can realize the 1: 1 transmission of the frequency signal of the instrument in the dangerous area to the safe area, and provide the isolated power supply (12V or 24V) for the field instrument in the dangerous area.
This product needs independent power supply, and the power supply, input and output are isolated between each other.
Specifications
Input in harzadous area | |
Input signal | Frequency ≤ 100kHz, amplitude ≤ 12V, duty cycle ≥ 20%, high-level ≥ 4V, low-level ≤ 1V (PHD-22TP-1313) Frequency ≤ 100kHz, amplitude ≤ 24V, duty cycle ≥ 20%, high-level ≥ 4V, low-level ≤ 1V (PHD-22TP-2323) |
Distribution voltage | Open circuit voltage ≤ 13V, distribution voltage ≥ 8.5V when loaded with 25mA (PHD-22TP-1313) Open circuit voltage ≤ 25V, distribution voltage ≥ 16V when loaded with 25mA (PHD-22TP-2323) |
Safety side output: | |
Output signal | Frequency quantity 1: 1 output |
Signal range | Signal low-level ≤ 0.5V Signal high level ≥ 10V (PHD-22TP-1313) Signal high level ≥ 20V (PHD-22TP-2323) |
Drive current | ≤ 15mA, load resistance ≥ 1k Ω |
Supply voltage | 20-35VDC |
Power consumption | When powered by 24VDC and output at 12V level ≤ 80mA (PHD-22TP-1313) ≤ 100mA (PHD-22TP-2323) |
LED indicator | Green: Power indicator |
Receiving and transmitting switching time | ≥20ms |
Temperature parameters | Working temperature: -20℃~+60℃ storage temperature:-40℃~+80℃ |
Relative humidity | 10%~95% RH no condensation |
Dielectric strength | Between intrinsically safe side and non-intrinsically safe side (≥ 3000VAC/min); between power supply and non-intrinsically safe terminal (≥ 1500VAC/min) |
Insulation resistance | ≥100MΩ (between input/output/power supply) |
Electromagnetic compatibility | According to IEC 61326-1(GB/T 18268), IEC 61326-3-1 |
MTBF | 100000h |
Wire requirements | Horizontal cutting surface ≥ 0.5mm2; Insulation strength ≥ 500V |
Applicable field equipments | Frequency measuring equipment |
Installation place | Installed in a safe zone, it can be connected to intrinsic safety instruments in hazardous areas up to Zone 0, IIC, Zone 20, and IIIC |
Intrinsically safe certification | |
Explosion proof mark | [Ex ia Ga]lIC [Ex ia Da]lllC |
Explosion-proof standard | GB/T3836.1-2021 GB/T3836.4-2021 |
PHD-22TP-1313 | |
Terminals 1-3、4-6 | Um:250V AC/DC Uo=17.8V DC lo=260mA Po=1.2W Co=0.22μF Lo=0.25mH |
Terminals 2-3、5-6 | Um:250V AC/DC Uo=8V DC lo=2.5mA Po=5mW Co=0.59μF Lo=100mH |
PHD-22TP-2323 | |
Terminals 1-3、4-6 | Um:250V AC/DC Uo=28V DC lo=93mA Po=0.65W Co=0.05μF Lo=0.56mH |
Terminals 2-3、5-6 | Um:250V AC/DC Uo=8V DC lo=2.5mA Po=5mW Co=0.05μF Lo=100mH |
Certification body | CQST(China National Quality Supervision and Test Centre for Explosion Protected Electrical Products) |
Dimension
Schematic diagram
Note:
1. The power rail function is an optional function, and users need to specify the power supply method when placing an order
The selection of power rail connectors can refer to page 89 of the "Annex"