PHD-22TP-1313 /PHD-22TP-2323

Frequency signal input isolated safety barrier

2 inputs 2 outputs

Frequency signal  Input 

Frequency signal 1: 1 Output 

Request a Quote

PRODUCTS DETAILS

Overview

The frequency signal is input into the isolated safety barrier, which can realize the 1: 1 transmission of the frequency signal of the instrument in the dangerous area to the safe area, and provide the isolated power supply (12V or 24V) for the field instrument in the dangerous area. 
This product needs independent power supply, and the power supply, input and output are isolated between each other.

Specifications

Input in harzadous area
Input signal Frequency ≤ 100kHz, amplitude ≤ 12V, duty cycle ≥ 20%, high-level ≥ 4V, low-level ≤ 1V (PHD-22TP-1313) Frequency ≤ 100kHz, amplitude ≤ 24V, duty cycle ≥ 20%, high-level ≥ 4V, low-level ≤ 1V (PHD-22TP-2323)
Distribution voltage Open circuit voltage ≤ 13V, distribution voltage ≥ 8.5V when loaded with 25mA (PHD-22TP-1313)
Open circuit voltage ≤ 25V, distribution voltage ≥ 16V when loaded with 25mA (PHD-22TP-2323)
Safety side output:
Output signal Frequency quantity 1: 1 output
Signal range Signal low-level ≤ 0.5V
Signal high level ≥ 10V (PHD-22TP-1313)
Signal high level ≥ 20V (PHD-22TP-2323)
Drive current ≤ 15mA, load resistance ≥ 1k Ω
Supply voltage 20-35VDC
Power consumption When powered by 24VDC and output at 12V level
≤ 80mA (PHD-22TP-1313)
≤ 100mA (PHD-22TP-2323)
LED indicator  Green: Power indicator
Receiving and transmitting switching time  ≥20ms
Temperature parameters Working temperature: -20℃~+60℃
storage temperature:-40℃~+80℃
Relative humidity 10%~95% RH no condensation
Dielectric strength Between intrinsically safe side and non-intrinsically safe side (≥ 3000VAC/min);
between power supply and non-intrinsically safe terminal (≥ 1500VAC/min)
Insulation resistance ≥100MΩ (between input/output/power supply)
Electromagnetic compatibility According to IEC 61326-1(GB/T 18268), IEC 61326-3-1
MTBF 100000h
Wire requirements Horizontal cutting surface ≥ 0.5mm2; Insulation strength ≥ 500V
Applicable field equipments Frequency measuring equipment
Installation place Installed in a safe zone, it can be connected to intrinsic safety instruments in hazardous areas up to Zone 0, IIC, Zone 20, and IIIC
Intrinsically safe certification
Explosion proof mark [Ex ia Ga]lIC [Ex ia Da]lllC
Explosion-proof standard GB/T3836.1-2021  GB/T3836.4-2021
PHD-22TP-1313
Terminals 1-3、4-6 Um:250V AC/DC Uo=17.8V DC lo=260mA
Po=1.2W Co=0.22μF Lo=0.25mH
Terminals 2-3、5-6 Um:250V AC/DC Uo=8V DC lo=2.5mA
Po=5mW Co=0.59μF Lo=100mH
PHD-22TP-2323
Terminals 1-3、4-6 Um:250V AC/DC Uo=28V DC lo=93mA
Po=0.65W Co=0.05μF Lo=0.56mH
Terminals  2-3、5-6 Um:250V AC/DC Uo=8V DC lo=2.5mA
Po=5mW Co=0.05μF Lo=100mH
Certification body CQST(China National Quality Supervision and Test Centre for Explosion Protected Electrical Products)

 

Dimension

PHD-11TP-1313、2323.jpg

Schematic diagram

PHD-11TP-1313、2323(2).jpg

Note:

1. The power rail function is an optional function, and users need to specify the power supply method when placing an order

The selection of power rail connectors can refer to page 89 of the "Annex"

 

Contact us

Please feel free to give your inquiry in the form below We will reply you in 24 hours

Leave YourMessage

Thank you! We will reply you via email within 24 hours.

return