PHD-12TZ-461

Two-wire or three-wire RTD Pt100 signal

1 output with RTD 1:1 signal, one output with 4~20mA signal

1 input 2 outputs

Request a Quote

PRODUCTS DETAILS

Overview

The thermistor input isolation safety barrier can convert the Pt100 signals of two wire and three wire thermistors (RTDs) in hazardous areas into one output with 1:1 RTD signal and one output with 4~20mA signal to the safety zone. It can be intelligently configured, and the actual range of the thermal resistance can be set through computer software. 

This product requires independent power supply, with isolated power supply, input, and output terminals.

Specifications

Specifications
Input in harzadous area  
Input signal Two wire or three wire Pt100 signal
Measurement range -200℃-850℃
Safety side output:
Output signal RTD Pt100 signal and 4~20mA signal
Load capacity Load capacity 0-500 Ω (customizable)
Supply voltage 20-35VDC
Power consumption ≤76mA (when 24VDC power supply, output 20mA) 
LED indicator  Green: Power indicator
Output accuracy 0.1%F.S
Temperature drift 0.1%F.S/10℃
Temperature parameters Working temperature: -20℃~+60℃, storage temperature:-40℃~+80℃
Relative humidity 10%~95% RH no condensation
Dielectric strength Between intrinsically safe side and non-intrinsically safe side (≥ 3000VAC/min);
between power supply and non-intrinsically safe terminal (≥ 1500VAC/min)
Insulation resistance ≥100MΩ (between input/output/power supply)
Electromagnetic compatibility According to IEC 61326-1(GB/T 18268), IEC 61326-3-1
MTBF 100000h
Wire requirements Horizontal cutting surface ≥ 0.5mm2; Insulation strength ≥ 500V
Applicable field equipments Two wire or three wire RTD Pt100
Installation place Installed in a safe zone, it can be connected to intrinsic safety instruments in hazardous areas up to Zone 0, IIC, Zone 20, and IIIC
Intrinsically safe certification
Explosion proof mark [Ex ia Ga]lIC [Ex ia Da]lllC
Explosion-proof standard GB/T3836.1-2021  GB/T3836.4-2021
Terminals 4-6、5-6 Um:250V AC/DC Uo=8.4V DC lo=31mA
Po=65.1mW Co=4.8μF Lo=20mH
Certification body CQST(China National Quality Supervision and Test Centre for Explosion Protected Electrical Products)

Dimension

PHD-12TZ-466(2).jpg

 Schematic diagram

PHD-12TZ-461.jpg

Note:

1. The power rail function is an optional function, and users need to specify the power supply method when placing an order

The selection of power rail connectors can refer to page 89 of the "Annex"

2. When inputting a three wire RTD, it is necessary to ensure that the three wires are of equal length as much as possible

3. When inputting a two-wire RTD, safety barrier terminals 4 and 2 must be short circuited

 

PHD-12TZ-461(1).jpg