PHD-12HD-211

Two or three-wire transmitter or current source input /4~20mA output
H Serie Backplane Mounting Isolated Safety Barriers
1 input 2 outputs

Request a Quote

PRODUCTS DETAILS

Overview

Isolated safety barrier at detection side: PHD-12HD-211, analog input and output, single input and dual output.
The isolated barrier can isolate and transmit the 4~20mA signal or DC 4~20 mA signal generated by the transmitter in the dangerous area to the safe area. When the transmitter is two-wire or three-wire system, the safety barrier provides power for the transmitter.
This product needs independent power supply.
This product supports HART signal and disconnection alarm.

Specifications

Supply voltage 20~35VDC, power consumption<1.5W (when supply power 24VDC, transmitter input, output 20mA)
Output power supply with provided power When the circuit output is 20mA, the provided voltage is≥16V
Input signal Two-wire or three-wire transmitter or current source signal (HART)
Output signal 4~20mA (HART)
Allowable output load capacity 0~500Ω (customizable)
Output accuracy 0.1%F.S (Typical value: 0.05% F.S)
Temperature drift 0.005% F.S/℃
Number of input and output 1 input 2 outputs
Applicable field equipments 2-wire, 3-wire transmitter and current source signal, this product is suitable for ABB, Fisher, Rosemount,
Honeywell 11, as well as 3351, EJA, SIEMENS and other products with imported technology
Temperature parameter Working temperature: -20℃~+60℃, storage temperature: -40℃~+80℃
Relative humidity 10%~95% RH no condensation
Insulation strength Between intrinsically safe side and non-intrinsically safe side (≥3000VAC/min);
between power supply and non-intrinsically safe side (≥1500VAC/min)
Insulation resistance ≥100MΩ (between input/output/power supply)
External dimensions Thickness 15.8mm * width 104.8mm * high 116.1mm
Electromagnetic compatibility According to IEC 61326-1 (GB/T 18268), IEC 61326-3-1
Explosion-proof mark [Exia Ga]IIC, [Exia Da]IIIC
Functional safety certification SIL2 according to IEC 61508 EN 61511 standards
Certification body CQST(China National Quality Supervision and Test Centre for Explosion Protected Electrical Products)
Certified parameters (between terminals 1-3)
Certified parameters (between terminals 2-3,2-1)
Um=250V    Uo=7.2V   Io=--          Po=--            Co=12μF        Lo=--
Um=250V    Uo=28V    Io=93mA  Po=0.65W   Co=0.083μF   Lo=4.2mH
Installation site requirements It can be connected with instruments in 0 zone with ⅡA, ⅡB, ⅡC dangerous gas
MTBF ≤100000h

 

Wiring diagram

Contact us

Please feel free to give your inquiry in the form below We will reply you in 24 hours