Overview
The isolated safety barriers with flame and smoke detectors input signals, which can provide isolation power for flame detectors in hazardous areas. The flame detector generates 0-40mA signals from the hazardous area and transmits them to the safe area, playing a smoke alarm role. This product adopts output loop power supply and is suitable for DCS/PLC systems with loop power supply.
This product does not require independent power supply, and the input and output terminals are isolated.
Specifications
Input in harzadous area | |
Input signal | 0~40mA |
Distribution voltage | Uo≥Ui-(280+RL)I-6,Ui≤24V Uo≥18-(280+RL)l,Ui>24V |
Short circuit current | ≤65mA (when powered by 24V) |
Safety side output: | |
Output signal | 0~40mA |
Signal power supply | 20-35VDC |
LED indicator | Green: power indication |
Transmission accuracy | <0.2F.S |
Response time | 2ms reaches 90% of the final value. |
Temperature drift | 0.01%F.S/℃ |
Temperature parameters | Working temperature: -20℃~+60℃ storage temperature:-40℃~+80℃ |
Relative humidity | 10%~95% RH no condensation |
Dielectric strength | Between intrinsically safe side and non-intrinsically safe side (≥ 3000VAC/min); between power supply and non-intrinsically safe terminal (≥ 1500VAC/min) |
Insulation resistance | ≥100MΩ (between input/output/power supply) |
Electromagnetic compatibility | According to IEC 61326-1(GB/T 18268), IEC 61326-3-1 |
MTBF | 100000h |
Wire requirements | Horizontal cutting surface ≥ 0.5mm2; Insulation strength ≥ 500V |
Applicable field equipments | Flame and smoke detector |
Installation place | Installed in a safe zone, it can be connected to intrinsic safety instruments in hazardous areas up to Zone 0, IIC, Zone 20, and IIIC |
Intrinsically safe certification | |
Explosion proof mark | [Ex ia Ga]lIC [Ex ia Da]lllC |
Explosion-proof standard | GB/T3836.1-2021 GB/T3836.4-2021 |
Terminals5-6, 2-3 | Um:250V AC/DC Uo=25.2V DC lo=93mA Po=586mW Co=0.083μF Lo=4.2mH |
Certification body | CQST(China National Quality Supervision and Test Centre for Explosion Protected Electrical Products) |
Dimension
Schematic diagram
Note:
PHD-11TN-11 does not include input 2 and output 2 parts