Overview
The isolated safety barrier with switch input transistor output, which isolates and transmits input signals from switch contacts or proximity switches in hazardous areas to of the safety zone with output transistor through the safety barrier. Line fault detection is achieved through LED on the top of the module. The dial switch of the module is used to set input and output in-phase or reverse control, as well as to enable or disable the line fault detection alarm indication function.
This product requires independent power supply, with isolated power supply, input, and output terminals.
Specifications
Specifications |
|
Input in harzadous area |
|
Input signal |
Switch contacts/proximity switches |
The supply voltage of the sensor |
About 8V |
Switching rate |
<5kHz |
Input/output characteristics: |
|
On site input current |
>2.1mA, the output is closed, indicating ON; |
Switched control between inverted phase and normal phase of outputs e-c |
When the dial switch K1 is at "ON", the transistor output e-c are in inverted phase |
Output in safe area |
|
Output signal |
Relay and alarm relay (optional) |
Output characteristic |
NPN type transistor emitter or collector open circuit output |
Drive capability |
Output current ≤ 20mA (1.2k Ω), maximum internal current 100mA, equipped with short-circuit current protection |
Basic parameters |
|
Supply voltage |
20~35VDC |
Power consumption |
<30mA(24V power supply, when the transistor is conducting) |
LED indicator |
Green: Power indicator |
Temperature parameters |
Working temperature: -20℃ ~ +60℃, |
Relative humidity |
10%~95% RH no condensation |
Insulation strength |
Between intrinsically safe side and non-intrinsically safe side (≥3000VAC/min); between power supply and non-intrinsically safe side (≥1500VAC/min) |
Insulation resistance |
≥100MΩ (between input/output/power supply) |
Electromagnetic compatibility |
According to IEC 61326-1 (GB/T 18268), IEC 61326-3-1 |
MTBF |
100000h |
Wire requirements |
Horizontal cutting surface ≥ 0.5mm2; Insulation strength ≥ 500V |
Applicable field equipments |
Field equipment such as dry contacts or NAMUR type proximity switch inputs that comply with DIN19234 standard |
Installation place |
Installed in a safe zone, it can be connected to intrinsic safety instruments in hazardous areas up to Zone 0, IIC, Zone 20, and IIIC |
Intrinsically safe certification |
|
Functional safety certification |
SIL3 according to IEC 61508 standards |
Explosion proof mark |
[Ex ia Ga]lIC [Ex ia Da]lllC |
Explosion-proof standard |
GB/T3836.1-2021 GB/T3836.4-2021 |
Terminals 3-4 |
Um:250V AC/DC Uo=10.5V DC lo=15mA |
Certification body |
CQST(China National Quality Supervision and Test Centre for Explosion Protected Electrical Products) |
Wiring diagram
Note:
1. The power supply of the power rail is an optional function. Users need to specify the power supply mode when ordering. Please refer to attachment on page 89.
Line Fault Detection
Users can select the "ON" side of the switch at the top of the module to enable fault detection function and indicate an alarm through the red LED light. On site input current>7mA, short circuit alarm (SC); On site input current<0.1mA, open circuit alarm (LB). If the switch contact input requires fault detection function (wire breakage, short circuit), a 22k Ω resistor should be connected in parallel at both ends of the switch, and a 680 Ω resistor should be connected in series (as shown in the wiring diagram for switch contact II).
Terminal assignments and dimensions
Terminal |
Terminal assignments |
|
9 |
Power supply + |
20~35VDC |
10 |
Power supply - |
|
3 |
Input+ |
|
4 |
Input- |
|
5 |
Transistor output+ |
|
6 |
Transistor output- |
|
7 |
Alarm relay output |
|
8 |
Alarm relay output |
Product Display