PHD-11TF-28

Digital Input Isolated Safety Barrier 

PHD-11TF-28 1 input and 1 output

Input: Switch contacts/proximity switches

Output: Transistor

Request a Quote

PRODUCTS DETAILS

Overview

The isolated safety barrier with switch input transistor output, which isolates and transmits input signals from switch contacts or proximity switches in hazardous areas to of the safety zone with output transistor through the safety barrier. Line fault detection is achieved through LED on the top of the module. The dial switch of the module is used to set input and output in-phase or reverse control, as well as to enable or disable the line fault detection alarm indication function.

 

This product requires independent power supply, with isolated power supply, input, and output terminals.

 

 

Specifications

 

 

Specifications

 

Input in harzadous area

 

Input signal

Switch contacts/proximity switches

The supply voltage of the sensor

About 8V

Switching rate

<5kHz

Input/output characteristics:

 

On site input current

>2.1mA, the output is closed, indicating ON;
When<1.2mA, the output is open circuit, indicating OFF

Switched control between inverted phase and normal phase of outputs e-c

When the dial switch K1 is at "ON", the transistor output e-c are in inverted phase
When the dial switch K1 is at "OFF", the transistor output e-c are in normal phase
When the K2 is at  "ON", the circut will select the red light LFD indication alarm function

Output in safe area

 

Output signal

Relay and alarm relay (optional)

Output characteristic

NPN type transistor emitter or collector open circuit output

Drive capability

Output current ≤ 20mA (1.2k Ω), maximum internal current 100mA, equipped with short-circuit current protection

Basic parameters

 

Supply voltage

20~35VDC

Power consumption

<30mA(24V power supply, when the transistor is conducting)

LED indicator

Green: Power indicator
Yellow: Output transistor in normal working state
Red: LFD indication, line fault alarm

Temperature parameters

Working temperature: -20℃ ~ +60℃,
Storage temperature: -40℃ ~ +80℃

Relative humidity

10%~95% RH no condensation

Insulation strength

Between intrinsically safe side and non-intrinsically safe side (≥3000VAC/min); between power supply and non-intrinsically safe side (≥1500VAC/min)

Insulation resistance

≥100MΩ (between input/output/power supply)

Electromagnetic compatibility

According to IEC 61326-1 (GB/T 18268), IEC 61326-3-1

MTBF

100000h

Wire requirements

Horizontal cutting surface ≥ 0.5mm2; Insulation strength ≥ 500V

Applicable field equipments

Field equipment such as dry contacts or NAMUR type proximity switch inputs that comply with DIN19234 standard

Installation place

Installed in a safe zone, it can be connected to intrinsic safety instruments in hazardous areas up to Zone 0, IIC, Zone 20, and IIIC

Intrinsically safe certification

 

Functional safety certification

SIL3 according to IEC 61508 standards

Explosion proof mark

[Ex ia Ga]lIC [Ex ia Da]lllC

Explosion-proof standard

GB/T3836.1-2021  GB/T3836.4-2021

Terminals 3-4

Um:250V AC/DC Uo=10.5V DC lo=15mA
Po=39.4mW Co=1.7μF Lo=165mH

Certification body

CQST(China National Quality Supervision and Test Centre for Explosion Protected Electrical Products)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wiring diagram

 

Note: 

 

1. The power supply of the power rail is an optional function. Users need to specify the power supply mode when ordering. Please refer to attachment on page 89.

Line Fault Detection

Users can select the "ON" side of the switch at the top of the module to enable fault detection function and indicate an alarm through the red LED light. On site input current>7mA, short circuit alarm (SC); On site input current<0.1mA, open circuit alarm (LB). If the switch contact input requires fault detection function (wire breakage, short circuit), a 22k Ω resistor should be connected in parallel at both ends of the switch, and a 680 Ω resistor should be connected in series (as shown in the wiring diagram for switch contact II).

 

 

Terminal assignments and dimensions

 

 

Terminal

Terminal assignments

9

Power supply +

2035VDC

10

Power supply -

3

Input+

4

Input-

5

Transistor output+

6

Transistor output-

7

Alarm relay output

8

Alarm relay output

 

 

Product Display

 

 

Contact us

Please feel free to give your inquiry in the form below We will reply you in 24 hours

Leave YourMessage

Thank you! We will reply you via email within 24 hours.

return