PHD-11TD-21+ / PHD-12TD-211+

Surge Protection Type Analogue Input Isolated Safety Barrier 
PHD-11TD-21+   1 input and 1 output
PHD-12TD-211+ 1 input and 2 outputs

Input: two or three-wire transmitter or current source(HART digital signal)
Output: 4~20mA (HART digital signal)

Request a Quote

PRODUCTS DETAILS

Overview

The analog input isolated safety barrier with surge protection function provides isolated power supply for two - and three wire transmitters in hazardous areas. The 4-20mA signal generated by the transmitter or current source is transmitted from the hazardous area to the safe area output, thereby driving the load in the safe area. For two - or three wire transmitters or current source signals, this safety barrier supports bidirectional communication of the Hart digital signal superimposed on the 4-20mA signal and has a wire breakage alarm function.

This product requires independent power supply, with isolated power supply, input, and output terminals.

Specifications

Input in harzadous area
Input signal Two or three-wire transmitter or current source(HART digital signal)
Transmitter distribution voltage The open circuit voltage is ≤28V, and the output voltage is ≥15.5V when the circuit is 20mA.
Output in safe area
Output signal 4~20 mA(HART  digital signal)
Output load When outputting 20mA, 0~500 Ω (customizable)
Optional voltage output type, load resistance RL ≥ 330k Ω
Surge protection features:  
Nominal discharge current ln(8/20μs) 5kA
Voltage protection level Up(8/20μs): 60V(line to line)
Voltage protection level Up(8/20μs): 600V(line to ground)
According to standards GB/T18802.21-2016(equivalent to 1EC61643-21:2012)
Basic parameters
Supply voltage 20~35VDC
Power consumption When 24V power supply, 20mA output
≤65mA(PHD-11TD-21+)
≤95mA(PHD-12TD-211+)
LED indicator  Green: power indicator
Response time 2ms to reach 90% of the final value
Temperature drift 0.005% F.S/℃
Temperature parameters Working temperature: -20℃ ~ +60℃,
Storage temperature: -40℃ ~ +80℃
Relative humidity 10%~95% RH no condensation
Insulation strength Between intrinsically safe side and non-intrinsically safe side (≥3000VAC/min); between power supply and non-intrinsically safe side (≥1500VAC/min)
Insulation resistance ≥100MΩ (between input/output/power supply)
Electromagnetic compatibility According to IEC 61326-1 (GB/T 18268), IEC 61326-3-1
MTBF 100000h
Wire requirements Horizontal cutting surface ≥ 0.5mm2; Insulation strength ≥ 500W
Applicable field equipments Two, three-wire (HART) transmitter or current source (HART) signal
Installation place Installed in a safe zone, it can be connected to intrinsic safety instruments in hazardous areas up to Zone 0, IIC, Zone 20, and IIIC
Intrinsically safe certification
Explosion proof mark [Ex ia Ga]lIC [Ex ia Da]lllC
Explosion-proof standard GB/T3836.1-2021  GB/T3836.4-2021
Terminals 5-6、5-4 Um:250V AC/DC Uo=28V DC lo=93mA Po=0.65W Co=0.083μF Lo=4.2mH
Terminal 4-6 Um:250V AC/DC Uo=7.2V DC lo=--- Po=-Co=12μF Lo=--
Certification body CQST(China National Quality Supervision and Test Centre for Explosion Protected Electrical Products)
Shanghai lightning protection products testing center

Dimension

PHD-11TD-21+.jpg

Connection wiring

PHD-11TD-21+(1).jpg

 

Note: 
1. PHD-11TD-21+ does not include output 2 part. 
2. The power supply of the power rail is an optional function. Users need to specify the power supply mode when ordering. Please refer to attachment on page 89.

Contact us

Please feel free to give your inquiry in the form below We will reply you in 24 hours

Leave YourMessage

Thank you! We will reply you via email within 24 hours.

return