PHD-11TC-33*

Isolated Safety Barrier at Detection Side
PHD-11TC-33

RS485 half-duplex input /RS485 half-duplex output    1 input 1 output

Request a Quote

PRODUCTS DETAILS

Overview

Isolated safety barrier at detection end: PHD-11TC-33*, communication signal input, single input and single output. The safety barrier can realize the bilateral communication of half duplex digital signals between RS485 interface in dangerous area and RS485 interface in safe area. 
This product needs an external 20-35VDC power supply.
The product is equipped with signal status indicator (yellow) 


In model letter: PHD-11C-33* the character "*" represents the provided voltage, and the regulations are as follows:

Code Provided voltage, current
No No provided power
A 5V
B 6V
C 12V
F 24V
H User defined

* bus terminal power supply, please see appendix for details.

 

Specifications

Supply voltage

20~35VDC, power consumption <2.5W  (24VDC, when provided power supply is 5 V with 80mA load)

Input signal

RS485 half-duplex digital signal

Output signal

RS485 half-duplex digital signal

Number of input and output channels

1 input 1 output

Applicable field equipments

Equipment with RS485 half-duplex communication interface

Transmission rate

Transmission rate ≤115.2kbps

Transmission delay

≤10 μs

Sending and receiving switching time

≥20ms

Temperature parameters

Working temperature: -20℃~+60℃, storage temperature:-40℃~+80℃

Relative humidity

10%~95% RH no condensation

Dielectric strength

Between intrinsically safe side and non-intrinsically safe side (≥ 3000VAC/min); between power supply and non-intrinsically safe terminal (≥ 1500VAC/min)

Insulation resistance

≥100MΩ (between input/output/power supply)

External dimensions

Thickness 12.5mm x width 108mm x high 118mm

Electromagnetic compatibility

According to IEC 61326-1(GB/T 18268), IEC 61326-3-1

Explosion-proof mark

[Exia Ga]IIC

Certification Body

CQST(China National Quality Supervision and Test Centre for Explosion Protected Electrical Products)

Authentication parameters (between terminals 1-2)

Um=250V  Uo=17.85V  Io=250mA  Co=0.22μF  Lo=0.25mH  Po=1.12W

Authentication parameters (between terminals 3-4)

Um=250V  Uo=7.7V  Io=80mA  Co=6.9μF  Lo=5.0mH  Po=0.15W

Installation site Requirements

It can be connected with instruments in 0 zone with ⅡA, ⅡB, ⅡC dangerous gas

MTBF

≤100000h

 

Wiring diagram

Terminal assignments and dimensions

Terminal

Terminal assignments

9

Power supply +

20~35VDC

10

Power supply -

3

Intrinsically safe side RS485-A

4

Intrinsically safe side RS485-B

1

Provided power supply+

2

Provided power supply-

6

RS485-A

7

RS485-B

 

Contact us

Please feel free to give your inquiry in the form below We will reply you in 24 hours

Leave YourMessage

Thank you! We will reply you via email within 24 hours.