Overview
Isolated safety barrier: PHD-11HZ-*1, RTD signal input, one input and one output.
The isolated safety barrier can convert the RTD input signal in hazardous area to 4~20mA signal output and transmit it to the safe area. The circuit is equipped with single RTD signal input and DC signal output.
The output 4~20mA signal, can be intelligently configured. The actual range of RTD can be set by computer.
PHD-11HZ-*1, "*" indicates the input type of RTD, please use the code to indicate. This product needs independent power supply.
Input signal types and measurement range | ||||
Code | RTD model | Measurement range | Minimum range | Conversion accuracy |
1 | G53 | -50~150℃ | 20℃ | 0.2℃/0.1% |
2 | G50 | -50~150℃ | 20℃ | 0.2℃/0.1% |
4 | Pt100 | -200~850℃ | 20℃ | 0.2℃/0.1% |
6 | Pt1000 | -200~850℃ | 20℃ | 0.2℃/0.1% |
7 | Ni1000 | -60~250℃ | 20℃ | 0.2℃/0.1% |
Example: Isolated safety barrier Pt100 input, temperature range 0~400℃, the output channel 1 is 4~20mA, the power supply is 20~35VDC, the model is PHD-11HZ-41(0~400℃), the measurement range can be set to the specified range of 0~400℃ by computer.
Specifications
Supply voltage | 20~35VDC, power consumption<1.2W (when power supply 24VDC, output 20mA) |
Input signal | Two-wire or three-wire RTD |
Output signal | 4~20mA |
Signal and measurement range | Signal range: corresponding to the measurement range of RTD Measurement range: When make an order, the user shall make the configuration by himself, which shall be indicated in the tail number or extra explained |
Allowable output load capacity | 0~500Ω (customizable) |
Alarm indication | L1 light is on at low-measurement range alarm; L2 light is on at high-measurement range alarm |
Channel number of input and output | 1 input 1 output |
Applicable field equipments | 2-wire or 3-wire RTD (G53, Cu50, Pt100, Pt1000, Ni1000) |
Output accuracy | 0.1%F.S (Typical value: 0.05%F.S) |
Temperature drift | 0.005%F.S/℃ |
Temperature parameter | Working temperature: -20℃~+60℃, storage temperature: -40℃~+80℃ |
Relative humidity | 10%~95% RH no condensation |
Dielectric strength | Between intrinsically safe side and non-intrinsically safe side (≥3000VAC/min);between power supply and non-intrinsically safe side (≥1500VAC/min) |
Insulation resistance | ≥100MΩ (between input/output/power supply) |
External dimensions | Thickness 15.8mm * width 104.8mm * high 116.1mm |
Electromagnetic compatibility | According to IEC 61326-1 (GB/T 18268), IEC 61326-3-1 |
Explosion-proof mark | [Exia Ga]IIC, [Exia Da]IIIC |
Certification body | CQST(China National Quality Supervision and Test Centre for Explosion Protected Electrical Products) |
Certified parameters (between terminals 1-3,2-3) | Um=250V Uo=8.4V Io=31mA Po=65.1mW Co=4.8μF Lo=20mH |
Installation site requirements | It can be connected with instruments in 0 zone with ⅡA, ⅡB, ⅡC dangerous gas |
MTBF | ≤100000h |
Wiring diagram