PHC-11TF-16

Digital Output Isolated Safety Barrier 
PHC-11TF-16  1 input and 1 output

Input: Switch contacts, logic levels
Output: 12V/60mA driver

Request a Quote

PRODUCTS DETAILS

Overview

The switching output isolated safety barrier drives the on-site intrinsically safe equipment in the hazardous area through the contact switch and logic level signal control in the safe area. Thereby controlling solenoid valves, sound and light alarms, etc. The signal status indicator light is set in red and yellow colors, the alarm displays red, and the output solenoid valve and other working tasks display yellow.
This product needs to be powered independently, and the power supply, input and output terminals are isolated between each other.

 

Specifications

Input in safe area
Input signal Switch contact, logic level
Dangerous side output:
Open circuit voltage 22V~24V DC, UE/IE=12V/35mA
Inversion function  K1 is set to the ON side, and the circuit output is inverted.
Basic parameters
Supply voltage 20~35VDC
Power consumption ≤70mA(24V power supply, when 12V/35mA power distribution)
LED indicator  Green: Power indicator
Yellow: Output relay in normal working state
Alarm relay function When dial switch K2 is at "ON" side, circuit selection alarm function
Load resistance <50Ω, short circuit alarm (SC)
Load resistance>10kΩ, open circuit alarm (LB)
Characteristic response time of alarm relay Response time: 20ms
Driving capacity: 250VAC/2A, 30VDC/2A resistive load
Load type: Resistive load
Output accuracy  0.1%F.S (typical value: 0.05%F.S)
Response time  20ms to reach 90% of final value
Temperature parameters Working temperature: -20℃ ~ +60℃,
Storage temperature: -40℃ ~ +80℃
Relative humidity 10%~95% RH no condensation
Insulation strength Between intrinsically safe side and non-intrinsically safe side (≥3000VAC/min); between power supply and non-intrinsically safe side (≥1500VAC/min)
Insulation resistance ≥100MΩ (between input/output/power supply)
Electromagnetic compatibility According to IEC 61326-1 (GB/T 18268), IEC 61326-3-1
MTBF 100000h
Wire requirements Horizontal cutting surface ≥ 0.5mm2; Insulation strength ≥ 500V
Applicable field equipments Audible and visual alarm, intrinsically safe solenoid valve
Installation place Installed in a safe zone, it can be connected to intrinsic safety instruments in hazardous areas up to Zone 0, IIC, Zone 20, and IIIC
Intrinsically safe certification
Explosion proof mark [Ex ia Ga]lIC [Ex ia Da]lllC
Explosion-proof standard GB/T3836.1-2021  GB/T3836.4-2021
Terminals 3-4 Um:250V AC/DC Uo=25.2V DC lo=85mA
Po=0.535W Co=0.107μF Lo=6mH
Certification body CQST(China National Quality Supervision and Test Centre for Explosion Protected Electrical Products)

 

Dimension 

PHC-11TF-13.jpg

Schematic Drawings

PHC-11TF-13(1).jpg

Note: 
1. The power supply of the power rail is an optional function. Users need to specify the power supply mode when ordering. Please refer to attachment on page 89.