PHC-11HF-14

Contact and logic level input/switch driving output
H Serie Backplane Mounting Isolated Safety Barriers
1 input 1 output

Request a Quote

PRODUCTS DETAILS

Overview

H serie backplane mounting isolated safety barriers at operating side: PHC-11HF-14, digital input and output, single input and single output.
Safety barrier can convert the input quantity of contact switch and logic level in safety area into the driving quantity of intrinsically safe equipments, and output it to the field of dangerous area, so as to
control solenoid valve, audible and visual alarm, etc.
The status indicator has red and yellow light colors, when alarm then the light is red, when it is with the output solenoid valve, then the light is yellow.
This product needs independent power supply.

Specifications

Supply voltage 20~35VDC, power consumption<2.2W
Input signal Switch contact, logic level
Output signal Open circuit voltage>24V, UE/IE=12.8V/45mA
Inversion function: K1 is set to the "ON" side, the circuit output is inverted
Alarm relay function The dial switch K2 is set to the "ON" side, the circuit adopts the alarm function
Load Resistance<50Ω, short-circuit alarm (SC), load resistance>10KΩ, open circuit alarm (LB)
Alarm relay output characteristics Response time: 20ms, driving capacity: 250VAC/2A, 30VDC/2A under resistive load
Number of input and output 1 input 1 output
Applicable field equipments Safety solenoid valve, audible and visual alarm
Temperature parameters Working temperature: -20℃~+60℃, storage temperature: -40℃~+80℃
Relative humidity 10%~95% RH no condensation
Dielectric strength Between intrinsically safe side and non-intrinsically safe side (≥3000VAC/min); between power supply and non-intrinsically safe terminal (≥1500VAC/min)
Insulation resistance ≥100MΩ (between input/output/power supply)
External dimensions Thickness 15.8mm * width 104.8mm * high 116.1mm
Electromagnetic compatibility According to IEC 61326-1 (GB/T 18268), IEC 61326-3-1
Explosion-proof mark [Exia Ga]IIC, [Exia Da]IIIC
Functional safety certification SIL2 according to IEC 61508 EN 61511 standards
Certification body CQST (China National Quality Supervision and Test Centre for Explosion Protected Electrical Products)
Certified parameters (between terminals 2-1) Um:250VAC/DC Uo=25.2V Io=147mA Po=0.92W Co=0.107μF Lo=1.5mH
Installation site requirements It can be connected with instruments in 0 zone with ⅡA, ⅡB, ⅡC dangerous gas
MTBF ≤100000h

 