Technical data
Power supply characteristics | |
Power supply | 100~230V AC |
AC frequency | 50Hz~60Hz |
Power consumption | ≤ 7VA (220V AC power supply, relay excitation state) |
Input characteristics | |
Wire resistance | ≤ 15 Ω |
Input current | ≤ 50mA (220V AC power supply) |
Input device | Emergency stop button, safety door |
Output characteristics | |
Number of contacts | 3NO+1NC |
Contact material | AgSnO2+0.2 μmAu |
Contact type | Forced guidance |
Contact fuse protection | 10A gL/gG, NEOZED (normally open contact) 6A gL/gG, NEOZED (normally closed contact) |
Switching capacity(EN 60947-5-1) | AC-15,5A/230V;DC-13,5A/24V |
Mechanical lifespan | more than 107 times |
Time characteristics | |
Switch-on delay | |
Automatic reset | ≤300ms |
Manual Reset | ≤150ms |
Delay-on de-energisation | |
Emergency stop operation | ≤30ms |
Power failure | ≤300ms |
Recovery time | |
Emergency stop operation | ≤30ms |
Power failure | ≤500ms |
Supply short interruption | 20ms |
safety certification | |
Performance Level (PL) | PLe conform to EN ISO 13849 |
Security Category (Cat.) | Cat.4 conform to EN ISO 13849 |
Task Time (TM) | 20 years conform to EN ISO 13849 |
Diagnostic coverage (DC/DCavg) | 99% conform to EN ISO 13849 |
Safety Integrity Level (SIL) | SIL3 conform to IEC 61508,IEC 62061 |
Hardware Fault Tolerance(HFT) | 1 conform to IEC 61508,IEC 62061 |
Safe failure fraction(SFF) | 99% conform to IEC 61508,IEC 62061 |
Probability of hazardous failure (PFHd) | 3.09E-10/h conform to IEC 61508,IEC 62061 |
StopCategory | 0 conforms to EN 60204-1 |
10% average number of hazardous failure cycles of components (B10d) | |
DC13,Ue=24V | Ie 5A 2A 1A Cycles 300,000 2,000,000 7,000,000 |
AC15,Ue=230V | Ie 5A 2A 1A Cycles 200,000 230,000 380,000 |
Environmental characteristics | |
Electromagnetic compatibility | conform to EN 60947,EN 61000-6-2,EN 61000-6-4 |
Vibration frequency | 10Hz~55Hz |
Vibration amplitude | 0.35mm |
Ambient temperature | -20 ℃~+60 ℃ |
Storage temperature | -40 ℃~+85 ℃ |
Relative humidity | 10% to 90% |
Altitude | ≤ 2000m |
Insulation characteristics | |
Electrical clearance and creepage distance | conform to EN 60947-1 |
Overvoltage level | III |
Pollution level | 2 |
Protection level | IP20 |
Insulation strength | 1500V AC, 1 minute |
Rated insulation voltage | 250V AC |
Rated impulse voltage | 6000V (1.2/50us) |
External dimensions
Block diagram
Wiring diagram
(1) The instrument wiring adopts Pluggable connecting terminal ;
(2) The soft copper cross-sectional area of the input side wire must be greater than 0.5mm2, and the output side must be greater than 1mm2;
(3) The exposed length of the wire is about 8mm, which is locked by M3 screws;
(4) The output contacts must provide enough fuse protection connections;
(5) Copper conductor must withstand an ambient temperature of at least 75 ℃;
(6) Terminal screws can cause misoperation, heating, etc. Therefore, please tighten it according to the specified torque. Terminal screw tightening torque 0.5Nm.
Installation
Safety relays should be installed in control cabinets with at least IP54 protection level.Meanwhile, the installation and use should comply with the relevant provisions of GB 5226.1-2019 "Mechanical and Electrical Safety - Mechanical and Electrical Equipment - Part 1: General Technical Conditions".
The PH6103-3A1B series safety relays are all installed with DIN35mm guide rails. Installation steps are as follows
(1) Clamp the upper end of the instrument onto the guide rail;
(2) Push the lower end of the instrument into the guide rail.
Dismantling
Insert a screwdriver (blade width ≤ 6mm) into the metal latch at the lower end of the instrument panel;
Push the screwdriver upwards and pry the metal latch downwards;
Pull the instrument panel up and out of the guide rail.
Attention
Please verify whether the product packaging, product label model, and specifications are consistent with the purchase contract; Before installing and using safety relays, carefully read this manual; If you have any questions, please contact the Beijing Pinghe Technical Support Hotline at 400 711 6763; The safety relay should be installed in a control cabinet with at least IP54 protection level; Use 220V AC power supply for instrument power supply;
Maintenance
(1) Please regularly check whether the safety function of the safety relay is in good condition, and whether there are signs that the circuit or the original is tampered with or bypassed;
(2) Please follow the relevant safety regulations and operate according to the instructions in this instruction manual, otherwise it may lead to fatal accidents or loss of personnel and property;
(3) The products have undergone strict inspection and quality control before leaving the factory. If you find that the products are not working properly and suspect that the internal module is faulty, please contact the nearest agent or directly contact the technical support hotline 400 711 6763.
(4) Within six years from the date of delivery, all product quality problems during normal use shall be repaired by Pinghe free of charge.