PH6001-1B is a safety relay control module, which is suitable for isolation and conversion of DI/D0 signals in SIS system. It has 1 normally closed (NC) contact, and its internal circuit adopts Fail-safe technology, triple redundancy technology and contact welding protection technology.
Technical data
Power supply characteristics: | |
Power supply: | 24V DC |
Current loss: | ≤35mA(24V DC) |
Voltage range: | 16V~35V DC nonpolarity |
Input characteristics: | |
Input current: | ≤ 35mA (24V DC) |
Wire resistance: | ≤ 15 Ω |
Input device: | SIS system DI/DO signal matching |
Output characteristics: | |
Number of contacts: | 1NC |
Contact material: | AgSnO2 |
Contact fuse protection: | 5A (internal fuse blown protection) |
Contact capacity: | 5A/250V AC; 5A/24V DC |
Mechanical lifespan: | more than 107 times |
Time characteristics: | |
Switch-on delay : | ≤ 30ms |
Delay-on de-energisation: | ≤ 30ms |
Recovery time: | ≤ 30ms |
Supply short interruption: | 20ms |
safety certification | |
Safety Integrity Level (SIL): | SIL3 conforms to IEC 61508 |
Hardware Fault Tolerance(HFT): | 0 conforms to IEC 61508 |
Safe failure fraction(SFF): | 99% conforms to IEC 61508 |
Probability of hazardous failure (PFHd): | 1.00E-09 /h conforms to IEC 61508 |
StopCategory: | 0 conforms to EN 60204-1 |
10% average number of hazardous failure cycles of components (B10d): | |
Rated Voltage 24VDC , L/R=7ms : | Ie 2A 1A 0.5A Cycles 180,000 300,000 400,000 |
Rated Voltage 230VAC , cos φ= At 0.4: | Ie 2A 1A 0.5A Cycles 500,000 580,000 600,000 |
Environmental characteristics | |
Electromagnetic compatibility: | conform to EN 60947,EN 61000-6-2,EN 61000-6-4 |
Vibration frequency: | 10Hz~55Hz |
Vibration amplitude: | 0.35mm |
Ambient temperature: | -20 ℃~+60 ℃ |
Storage temperature: | -40 ℃~+85 ℃ |
Relative humidity: | 10% to 90% |
Altitude: ≤ 2000m | ≤2000m |
Insulation characteristics | |
Electrical clearance and creepage distance: | conform to EN 60947-1 |
Overvoltage level: | III |
Pollution level: | 2 |
Protection level: | IP20 |
Insulation strength: | 1500V AC, 1 minute |
Rated insulation voltage: | 250V AC |
Rated impulse voltage: | 6000V (1.2/50us) |
Wiring diagram
Functional Block Diagram
Typical application
Wiring diagram
(1) The instrument wiring adopts Pluggable connecting terminal ;
(2) The soft copper cross-sectional area of the input side wire must be greater than 0.5mm2, and the output side must be greater than 1mm2;
(3) The exposed length of the wire is about 8mm, which is locked by M3 screws;
(4) The output contacts must provide enough fuse protection connections;
(5) Copper conductor must withstand an ambient temperature of at least 75 ℃;
(6) Terminal screws can cause misoperation, heating, etc. Therefore, please tighten it according to the specified torque. Terminal screw tightening torque 0.5Nm.
Installation
Safety relays should be installed in control cabinets with at least IP54 protection level.
The PH6001-1A series safety relays are all installed with DIN35mm guide rails. Installation steps are as follows
(1) Clamp the upper end of the instrument onto the guide rail;
(2) Push the lower end of the instrument into the guide rail.
Dismantling
Insert a screwdriver (blade width ≤ 6mm) into the metal latch at the lower end of the instrument panel;
Push the screwdriver upwards and pry the metal latch downwards;
Pull the instrument panel up and out of the guide rail.
Attention
Please verify whether the product packaging, product label model, and specifications are consistent with the purchase contract;
Before installing and using safety relays, carefully read this manual;
If you have any questions, please contact the Beijing Pinghe Technical Support Hotline at 400 711 6763;
The safety relay should be installed in a control cabinet with at least IP54 protection level;
The instrument is powered by 24V power supply, and the use of 220V AC power supply is strictly prohibited;
Maintenance
(1) Please regularly check whether the safety function of the safety relay is in good condition, and whether there are signs that the circuit or the original is tampered with or bypassed;
(2) Please follow the relevant safety regulations and operate according to the instructions in this instruction manual, otherwise it may lead to fatal accidents or loss of personnel and property;
(3) The products have undergone strict inspection and quality control before leaving the factory. If you find that the products are not working properly and suspect that the internal module is faulty, please contact the nearest agent or directly contact the technical support hotline.
(4) Within six years from the date of delivery, all product quality problems during normal use shall be repaired by Pinghe free of charge.