PH6001-1B is a safety relay control module, which is suitable for isolation and conversion of DI/D0 signals in SIS system. It has 1 normally closed (NC) contact, and its internal circuit adopts Fail-safe technology, triple redundancy technology and contact welding protection technology.

Technical data

Power supply characteristics:
Power supply: 24V DC
Current loss:  ≤35mA(24V DC) 
Voltage range:  16V~35V DC nonpolarity
Input characteristics:
Input current:  ≤ 35mA (24V DC)
Wire resistance:  ≤ 15 Ω
Input device:  SIS system DI/DO signal matching
Output characteristics:
Number of contacts:  1NC
Contact material:  AgSnO2
Contact fuse protection:  5A (internal fuse blown protection)
Contact capacity:  5A/250V AC; 5A/24V DC
Mechanical lifespan:  more than 107 times
Time characteristics:
Switch-on delay :  ≤ 30ms 
Delay-on de-energisation:  ≤ 30ms 
Recovery time:  ≤ 30ms 
Supply short interruption:  20ms
safety certification
Safety Integrity Level (SIL):   SIL3    conforms to IEC 61508
Hardware Fault Tolerance(HFT):   0           conforms to IEC 61508
Safe failure fraction(SFF):  99%     conforms to IEC 61508
Probability of hazardous failure (PFHd):  1.00E-09 /h   conforms to IEC 61508
StopCategory:   0        conforms to EN 60204-1
10% average number of hazardous failure cycles of components (B10d):  
Rated Voltage 24VDC , L/R=7ms : Ie              2A          1A       0.5A
Cycles 180,000  300,000  400,000
Rated Voltage 230VAC , cos φ= At 0.4: Ie                 2A          1A         0.5A
Cycles   500,000   580,000    600,000

 

Environmental characteristics
Electromagnetic compatibility:  conform to EN 60947,EN 61000-6-2,EN 61000-6-4
Vibration frequency:  10Hz~55Hz
Vibration amplitude:  0.35mm
Ambient temperature:   -20 ℃~+60 ℃
Storage temperature:   -40 ℃~+85 ℃
Relative humidity:  10% to 90%
Altitude: ≤ 2000m ≤2000m
Insulation characteristics
Electrical clearance and creepage distance: conform to EN 60947-1
Overvoltage level:  III
Pollution level:  2
Protection level:  IP20
Insulation strength:  1500V AC, 1 minute
Rated insulation voltage:  250V AC
Rated impulse voltage:  6000V (1.2/50us)

 

Wiring diagram

PH6001-1B(1).png

Functional Block Diagram

PH6001-1B(2).png

Typical application

PH6001-1B(3).png

PH6001-1B(4).png

Wiring diagram

(1) The instrument wiring adopts Pluggable connecting terminal ;
(2) The soft copper cross-sectional area of the input side wire must be greater than 0.5mm2, and the output side must be greater than 1mm2;
(3) The exposed length of the wire is about 8mm, which is locked by M3 screws;
(4) The output contacts must provide enough fuse protection connections;
(5) Copper conductor must withstand an ambient temperature of at least 75 ℃; 
(6) Terminal screws can cause misoperation, heating, etc. Therefore, please tighten it according to the specified torque. Terminal screw tightening torque 0.5Nm.

PH6001-1B(5).png

 

Installation

Safety relays should be installed in control cabinets with at least IP54 protection level.
The PH6001-1A series safety relays are all installed with DIN35mm guide rails. Installation steps are as follows
(1) Clamp the upper end of the instrument onto the guide rail;  
(2) Push the lower end of the instrument into the guide rail.

PH6001-1B(6).png

Dismantling

Insert a screwdriver (blade width ≤ 6mm) into the metal latch at the lower end of the instrument panel;
Push the screwdriver upwards and pry the metal latch downwards;
Pull the instrument panel up and out of the guide rail.

PH6001-1B(7).png

Attention

Please verify whether the product packaging, product label model, and specifications are consistent with the purchase contract;
Before installing and using safety relays, carefully read this manual;
If you have any questions, please contact the Beijing Pinghe Technical Support Hotline at 400 711 6763;
The safety relay should be installed in a control cabinet with at least IP54 protection level;
The instrument is powered by 24V  power supply, and the use of 220V AC power supply is strictly prohibited;

 

Maintenance

(1) Please regularly check whether the safety function of the safety relay is in good condition, and whether there are signs that the circuit or the original is tampered with or bypassed;
(2) Please follow the relevant safety regulations and operate according to the instructions in this instruction manual, otherwise it may lead to fatal accidents or loss of personnel and property;
(3) The products have undergone strict inspection and quality control before leaving the factory. If you find that the products are not working properly and suspect that the internal module is faulty, please contact the nearest agent or directly contact the technical support hotline.
(4) Within six years from the date of delivery, all product quality problems during normal use shall be repaired by Pinghe free of charge.

Contact us

Please feel free to give your inquiry in the form below We will reply you in 24 hours

Leave YourMessage

Thank you! We will reply you via email within 24 hours.

return