无

PHD-22HT-*1*1

PHD-22HT-*1*1   2 inputs and 2 outputs

Input signal: K, S, E, J, B, T, R, N thermocouple signals (see "Input Signal Types and Ranges Table")

Output signal: 4~20mA

Request a Quote

PRODUCTS DETAILS

Products Categories
Featured Products

PHD-22HT-*1*1

PHD-22HT-*1*1   2 inputs and 2 outputs

Input signal: K, S, E, J, B, T, R, N thermocouple signals (see "Input Signal Types and Ranges Table")

Output signal: 4~20mA

  • 简介: 20kg
  • 产品分类: Interior wall
  • 产品类型: Finish
  • 关键词: Matt
  • 产品链接: No

Overview

The PHD-22HT-*1*1 converts a low level DC signal (TC) from a temperature sensor in a hazardous area to a 4~20mA current signal for driving a safe area load. This product has a built-in cold end compensation function, can be intelligently configured, and the actual range range of the thermocouple can be set through the computer software. It has broken wire alarm function and out of range alarm function. The product requires a separate power supply with triple isolation for power, input and output. "*" indicates the thermocouple input type, the specific model with the code (see the figure below)


Input signal types and measurement range

Code

RTD model

Measurement range

Minimum range

Conversion accuracy

1

K

 -200~1370℃

50℃

0.5℃/0.1%S

2

S

 -50~1760℃

500℃

1.5℃/0.1%E

3

E

 -140~1000℃

50℃

0.5℃/0.1%s

4

J

 -160~1200℃

50℃

0.5℃/0.1%

5

B

 250~1800℃

500℃

1.5℃/0.1%R

6

T

 200~4000℃

50℃

0.5℃/0.1%

7

R

 -50~17600℃

500℃

1.5℃/0.1%R

8

N

 -200~1300℃

50℃

0.5℃/0.1%


 

 


Main technical parameters

 

Number of channels:

two inputs and two outputs

Power supply:

 

Power supply voltage:

20~35V DC, power consumption of about 2W (24V DC, output 20mA)

Power protection:

power reverse protection

Hazardous side input:

 

Input Signal:

K, S, E, J, B, T, R, N thermocouple signals (see "Input Signal Types and Ranges Table")

Signal range:

Corresponding to the measurement range of thermocouple -10~100mV.

Measuring range:

the user to develop their own configuration when ordering, specified in the end number or other instructions

Built-in cold end compensation:

±1℃ (compensation range -20℃~+60℃)

Safety side output:

 

Output signal:

4~20mA

Allowable Output Load Capacity:

0~500Ω (Customizable)

LED indicator:

Green ⸺Power indicator; yellow light on for low range alarm; red light on for high range alarm.

Output accuracy:

See "Input signal type and range table".

Response time:

500ms to 90% of final value

Temperature Drift:

0.005%F.S/°C

Temperature parameters:

operating temperature -20℃~+60℃; storage temperature -40℃~+80℃

Air relative humidity:

10%~95%RH without condensation

Insulation strength:

intrinsically safe end and non-intrinsically safe end (≥3000V AC/min); between power supply and non-intrinsically safe (≥1500V AC/min)

Insulation resistance:

≥100MΩ (input/output/power supply between)

Electromagnetic compatibility:

in line with IEC 61326-1 (GB/T 18268), IEC 61326-3-1

Mean time to failure:

100000 hours

Wire requirements:

cross-section ≥ 0.5mm2; insulation strength ≥ 500V

Applicable field devices:

Applicable field devices: K, S, E, J, B, T, R, N thermocouple sensor

Installation site:

installed in the safe zone, can be connected with the highest in Zone 0, IIC, Zone 20, IIIC hazardous locations of the intrinsically safe instrumentation

Safety certification

 

Certification body:

National Explosion-proof Electrical Product Quality Supervision and Testing Center CQST

Certification standard:

GB/T 3836.1-2021, GB/T 3836.4-2021

Explosion-proof symbol:

[Exia Ga]ⅡC, [Exia Da]ⅢC

Certified parameters (between terminals 1-2):

Um: 250V AC/DC, Uo=8.4V DC, Io=31mA,
Po=65.1W, Co=4.8μF, Lo=20mH.

PHD-22HT-X1X1



Download_file
PHD-11TC-33A-23


Related products

Contact us

Please feel free to give your inquiry in the form below We will reply you in 24 hours

Leave YourMessage

Thank you! We will reply you via email within 24 hours.

Return