A safety relay is an electrical control device that implements safety functions such as emergency stop and interlocking by means of proven components and safety design principles, using redundancy, self-monitoring and diagnostics.
In a safety instrumented system (SIS), it is the key actuating and isolating element that links the controller with the final elements and realizes the safety interlock function.
One concept that is easily confused should be clarified first: what is commonly called a “safety relay” actually covers two levels —
- Relay component level:a relay with force-guided (mechanically linked) contacts, specified in IEC 61810-3; it is the basic element from which a safety function is built;
- Device (module) level:a safety relay module/device that integrates redundancy, self-monitoring and diagnostics and can directly perform safety logic processing and output (e.g., an emergency-stop safety relay module).
The former is a “component”, the latter a “complete unit”. Both belong to the topic of “safety relays”, but their failure mechanisms and selection criteria differ, and the two should not be conflated in practical applications.
It is worth noting that a “safety relay” is not a “relay without faults” or a “relay that never fails”, but a relay that takes a deterministic (rule-based) action when a fault occurs. Its essential difference from an ordinary relay lies in its force-guided (mechanically linked) contact structure and its redundancy and self-monitoring mechanisms, which still deliver a definite, predictable safety response when a fault occurs.
Main Features of Safety Relays
Safety Characteristics
Force-guided (mechanically linked) contact structure: even if a contact welding fault occurs, it is ensured that the normally open (NO) and normally closed (NC) contacts cannot close at the same time, fundamentally preventing the loss of protection caused by contact sticking in ordinary relays. This structure is specified in IEC 61810-3 (Electromechanical elementary relays – Part 3: Relays with forcibly guided (mechanically linked) contacts, which superseded EN 50205). The standard requires that when an NO contact welds, the NC contact linked to it must open reliably with a contact gap of not less than 0.5 mm; a relay in which all contacts satisfy the force-guided requirement is designated Type A. In addition, the relay must pass the “failure to open” test as well as type tests covering mechanical endurance (not less than 10 million operations), electrical endurance, etc.
Redundancy and self-monitoring: redundant and diverse structures, channel consistency checking and an anti-welding forced-opening mechanism are used to continuously monitor the relay’s own status; upon a fault, restart is blocked and the safe state is maintained.
Fail-safe: an ordinary control module loses its protection when it fails, whereas a safety module maintains functional safety through redundancy and self-monitoring and delivers a deterministic safety response even when a fault occurs.
Loop detection and diagnostic feedback: functions such as input loop detection and diagnostic feedback (e.g., EDM – external device monitoring) allow real-time monitoring of the safety signals and the output loop status.
Compliance with functional safety and machinery safety standards: the design meets the requirements of PL e (Category 4) of ISO 13849-1 and SIL 3 of IEC 61508, and can be applied in the machinery safety domain in accordance with IEC 62061.
|
Note · Functional safety certification (SIL): based on IEC 61508; the equivalent Chinese national standard is GB/T 20438. · Machinery safety certification (PL): based on ISO 13849-1; the equivalent Chinese national standard is GB/T 16855.1. · The top-level standard for SIS in the process industries is IEC 61511, with the equivalent national standard GB/T 21109; SIS design in the petrochemical industry additionally follows GB/T 50770-2013, *Code for Design of Safety Instrumented Systems in Petrochemical Plants*. The design, SIL determination and verification of the SIS should be governed by this framework. |

Figure 1 Typical system function block diagram of a safety relay
Typical safety relays are mostly used for input applications such as emergency-stop pushbuttons and safety door switches, providing 3 NO (normally open) safety output contacts and 1 NC (normally closed) auxiliary output contact, with selectable single/dual-channel operation, manual or automatic reset, and monitoring for short circuits between channels. In engineering practice, the redundant outputs are usually wired as two NO contacts in series and two NC contacts in parallel: with the two NO contacts in series, if either one welds, the other can still open reliably when the coil is de-energized, so the final element will not fail to de-energize because of a single welded contact; with the two NC contacts in parallel, if either one welds in the closed position, the feedback circuit still remains closed, and the controller judges this as “not released” and blocks restart, so the fault is not masked.

Figure 2 Principle of force-guided contacts in a safety relay and contact-state comparison
Differences Between Safety Relays and Ordinary Relays
Table 1 Comparison between safety relays and ordinary relays
|
Item |
Ordinary Relay |
Safety Relay |
|
Contact design |
Conventional contacts; the protection function may fail if a contact welds |
Force-guided contacts (IEC 61810-3); NO and NC contacts cannot close simultaneously even when one welds |
|
Redundant structure |
None |
Redundant, diverse structure + channel consistency checking |
|
Fault detection |
No self-testing capability |
Self-testing, automatic detection and diagnostic feedback |
|
Fault behaviour |
Non-deterministic |
Predictable (de-energize to trip / fail-safe) |
|
Safety certification |
None |
Compliant with ISO 13849-1, IEC 61508, etc. |
|
Applicable scenarios |
General control circuits |
SIS safety interlock loops |
|
Reliability and cost |
Lower cost |
More reliable and compliant, but with more complex control and higher cost |
Why Must an SIS Use Safety Relays?
The Fundamental Requirement of the Fail-Safe Principle
An SIS must follow the fail-safe principle: when the SIS fails due to internal or external causes, the protected plant shall shut down safely in a predetermined sequence and automatically move to the safe state. Concretely, this means:
- Normal operating conditions:the relay coil is energized and the output contacts are closed (the NO contacts conduct);
- Abnormal/fault conditions:the relay is de-energized, the contacts open and the interlock action is triggered.
The commonly adopted engineering practice is: while the interlock has not been triggered, the relay remains energized and the circuit is wired to the normally open (NO) contact; once the SIS or the power supply system fails, the relay de-energizes, the contact opens and the field solenoid valve acts accordingly.
This design is “de-energize to trip”: it ensures that the safety shutdown is still reliably executed even in the presence of latent faults such as broken wiring, power supply failure or relay failure, avoiding the risk of a failure to act when the equipment should have tripped.
Ordinary Relays Cannot Meet the Safety Requirements
In accordance with the fail-safe design principles of GB/T 50770-2013, *Code for Design of Safety Instrumented Systems in Petrochemical Plants*, and GB/T 21109 (identical to IEC 61511), the final elements of a safety interlock loop shall fail to the safe state. For relays the problem is inherent: an ordinary relay is not fail-safe — its contacts may weld together, or the spring may fail to return the switch contacts to the non-energized position.
Ordinary relays lack a force-guided structure, self-diagnostics and redundant design, and therefore cannot guarantee that:
- the relay still acts safely when its contacts weld;
- faults are detected and alarmed in a timely manner;
- the safety function is not lost under a single fault.
Note: the statement that “ordinary relays are not fail-safe” first appeared in SHB Z06-1999, *Design Guidelines for Emergency Shutdown and Safety Interlock Systems in Petrochemical Plants* (this industry guideline is still in force and has not been withdrawn). In current engineering design, SIS design, SIL determination and verification are mainly carried out in accordance with GB/T 50770-2013 and GB/T 21109.
Typical Application Scenarios in an SIS
In the process industries, safety relays often serve as the interface between the SIS logic solver and the final elements, providing logic output, electrical isolation and power driving. They are mainly used for:
- Signal isolation:interlock signals between the SIS and the MCC (motor control center) are isolated through safety relays, preventing high-energy interference from damaging the SIS cards;
- DO signal output:SIL 3 safety relays are added for isolation in the DO loops from the SIS to the solenoid valves and the MCC;
- DI signal input:DI signals from the MCC enter the SIS after isolation through SIL 3 safety relays;
- Final element driving:driving final elements such as solenoid valves and contactors to implement de-energize-to-trip interlocking.
Taking the Beijing Pinghe PH6000 series safety relay control module as an example, it is designed precisely for safety switch inputs and for DI/DO signal isolation and conversion in SIS systems. It offers a variety of contact configurations including 1NO, 1NC, 2NO and 1NO+1NC, and has obtained SIL 3 functional safety certification.

Figure 3 Typical application of safety relays (interface between the SIS and the final elements)
Meeting SIL Verification Requirements
The SIS performs safety functions, and every device incorporated in it must pass functional safety verification.
In the SIL verification of an SIF loop, the relay counts as an auxiliary device that participates in the SIL calculation. A safety relay should come with failure data and certification capability that satisfy the SIL target of the loop (SIL 3 capability is usually required), so as to ensure that the overall safety integrity level of the SIF loop meets the design requirements — the SIL level is ultimately determined by calculating the average probability of failure on demand (PFDavg) of the entire loop, not by rating any single device alone.
For motor-driven final elements, many SIL 2/SIL 3 interlocked pumps and motors in practice fail verification, mostly because of single-point outputs or the use of ordinary relays. In such cases, SIL 3-certified safety relays should be selected directly, in a 1oo2 (one-out-of-two) redundant output arrangement — two channels in series, so that the interlock is triggered when either channel operates.
Intelligent Applications
Safety relays employ dual/triple redundancy and contact-welding protection internally, and virtually all of them provide loop detection (able to detect faults in the external loop, such as a welded contactor contact) and diagnostic feedback (feeding their own status back to the SIS or PLC).
However, not all interposing relays in SIS loops have self-diagnostic capability. For relays without built-in self-diagnostics, diagnostic coverage of the relay output loop can still be achieved through external configuration and monitoring by the SIS logic solver (for example, by connecting auxiliary contact feedback).
Therefore, in SIS design and device selection, if the safety integrity requirement of the SIF loop in which the relay sits is high, it is advisable to choose a SIL-certified safety relay with self-diagnostics/fault feedback, or to include the relay contact status in the scope of SIS diagnostic monitoring. Note that self-diagnostics cannot cover all dangerous failures, and safety relays still require periodic offline proof testing (PTI). The Beijing Pinghe PH6000 series, for example, provides Proof Test terminals on the module (optional) so that offline verification of the relay contacts can be carried out quickly on site.
Points to Note in Design and Selection
Safety relays provide loop detection and diagnostic feedback, and their redundant structure eliminates single points of failure — which matches the redundancy-oriented design principles of the SIS.
SIS design emphasizes minimizing intermediate links to reduce the probability of failure. As a certified, modular device with integrated safety logic, a safety relay can directly and reliably perform the safety shutdown and monitoring, reducing the uncertainty and failure risk introduced by wiring up ordinary relays.
In interlock loops that require electrical isolation and power driving, SIL-certified safety relays should be preferred, so that the process can still be brought reliably to the safe state even when the relay itself fails or an external abnormality occurs; if the output module of a safety PLC is used to drive the final elements directly, it must likewise satisfy the SIL verification and diagnostic coverage requirements.
When selecting a safety relay, attention should also be paid to its timing characteristics — pick-up/drop-out delay, recovery time and tolerance to short supply interruptions — as well as application parameters such as operating temperature, power consumption and temperature rise, inrush current at power-up, and the proof test interval (PTI).
Safety relays are available in a variety of contact configurations, commonly 1NO, 1NC, 2NO and 1NO+1NC, as well as 2NO+2NC, 3NO+1NC, 5NO+1NC, 4NO+2NC and 3NO+3NC. Generally speaking, 1NO is sufficient to drive a single actuating loop; if one additional normally closed contact is needed for status feedback and diagnostics alongside the safety output, 1NO+1NC can be selected (a 1NC used on its own suits normally closed interlock loops); 2NO is appropriate for dual outputs or multi-loop driving; specifications with a larger number of contacts are mainly used where signal multiplication is required. The specific configuration should be chosen according to the number of loops, the interlocking method, and the redundancy/diagnostic requirements.
Beijing Pinghe’s SIS Safety Relays and Supporting Solutions
Safety relays are one of the core product lines of Beijing Pinghe.
Safety Relays (SIS Systems) · PH6000 Series
Designed for safety switch inputs and for DI/DO signal isolation and conversion in SIS systems, the series adopts fail-safe technology, triple redundancy and contact-welding protection internally, and has obtained SIL 3 functional safety certification. The modules reserve Proof Test terminals (indicated by “R” in the model number) for rapid offline verification of the relay contacts, and come with an extended six-year warranty.
Table 2 PH6000 series models
|
Model |
Contact Configuration |
Remarks |
|
PH6001-1A |
1NO |
Single channel, with Proof Test terminals (optional) |
|
PH6001-1B |
1NC |
Single channel, normally closed output |
|
PH6002-2A |
2NO |
Dual channel, with Proof Test terminals (optional) |
|
PH6003-1A |
1NO |
With Proof Test terminals (optional) |
|
PH6003-1B |
1NC |
Normally closed output |
|
PH6005-1AR1B-F |
1NO+1NC |
With Proof Test terminals; panel fuse holder pre-fitted with a 5 A fuse for quick replacement |
Main technical parameters (taking the PH6001-1A as an example):
- Supply voltage: 16–35 V DC; current consumption ≤ 35 mA (at 24 V DC)
- Switching capacity: 5 A / 230 V AC, 5 A / 24 V DC; contact fuse protection 5 A
- Timing characteristics: pick-up/drop-out delay ≤ 30 ms; recovery time ≤ 30 ms; tolerance to short supply interruptions 20 ms
- Operating temperature: −20 ℃ to +60 ℃
- Functional safety: Safety Integrity Level SIL 3
In addition, a safety relay series for mechanical systems is available, featuring dual-channel safety conditions, real-time monitoring of the two input channels, a guaranteed safety output even under a single functional fault, and feedback monitoring of the safety output.
Supporting Solutions
What safety relays solve is the reliable actuation and electrical isolation of on/off (discrete) interlocking. In the analog loops (4–20 mA) and intrinsically safe circuits of the SIS, however, signal isolation, explosion protection and surge protection additionally call for galvanically isolated safety barriers, signal isolators and surge protective devices. Beijing Pinghe can supply these products as a complete, coordinated package.

Figure 4 Beijing Pinghe PH6002 safety relay control module (PH6000 series)