I. Overview
In industrial automation control systems, the 4-20mA current signal is the most widely used analog signal transmission standard. Depending on whether the signal output end provides its own loop-driving power supply, 4-20mA signals can be divided into active signals and passive signals. Correctly distinguishing between the two is the foundation for instrument selection, wiring, and troubleshooting.
II. Active 4-20mA Signal
An active signal means the signal output device has its own power supply capability and can actively drive the current loop to output a 4-20mA current signal. The output port has an integrated power supply circuit and current regulation circuit, allowing it to operate without an external power source. Typical devices include: PLC analog output modules (AO modules), DCS analog output cards, variable-frequency drive frequency setpoint outputs, and the active output channels of signal isolators.
Main characteristics: the output end has its own power supply, so the receiving end needs no additional power supply and wiring is simple (direct two-wire connection); however, output capability is limited by the device's internal compliance voltage, and the total loop load resistance must not exceed the maximum allowable value. Note: an active output must not be connected directly to another active receiving end, otherwise the two overlapping power supplies may cause abnormal loop current or even damage the equipment.
III. Passive 4-20mA Signal
A passive signal means the signal device itself does not provide loop-driving power; an external DC power supply (typically 24V DC) must be connected in series in the loop to form a complete current loop. The device contains only a current regulation circuit, transmitting the measured signal by varying the loop current. Typical devices include: two-wire pressure/temperature/level transmitters, some two-wire electromagnetic flowmeters, and the passive output channels of signal isolators.
Main characteristics: the loop must have a 24V power supply connected in series to operate; a two-wire transmitter is both the signal source and the loop load, with the signal current (4-20mA) simultaneously powering the transmitter itself; the device's minimum operating current is 4mA, which limits the transmitter's power consumption. Loop configuration: 24V power supply positive terminal → transmitter → receiving device → 24V power supply negative terminal, forming a closed loop.
IV. Two-Wire vs. Four-Wire Transmitters
Two-wire transmitter: the power line and signal line share the same pair of cables, so it must be a passive signal, requiring an external 24V power supply connected in series in the loop. Four-wire transmitter: the power line and signal line are independent, using two separate pairs of cables — one for power and one for signal output. The signal output of a four-wire transmitter can be either active (the device has its own independent power supply) or passive, depending on the specific design.
V. Comparison of Active and Passive Signals
|
Comparison Item |
Active Signal |
Passive Signal |
|
Loop Power Supply |
Provided by output device |
Requires external 24V DC supply |
|
Output Port Nature |
Actively outputs current |
Passively regulates current |
|
Receiving End Requirement |
Passive receiving (current detection only) |
Connected in series in power loop |
|
Wiring Complexity |
Simple (direct two-wire connection) |
Requires series-connected power supply |
|
Typical Devices |
PLC AO module, DCS output card |
Two-wire transmitter |
|
Max Load Resistance |
Limited by compliance voltage |
Limited by supply voltage |
VI. Product Selection and Beijing Pinghe Product Recommendations
In practical engineering, distinguishing between active and passive signals directly determines the selection of isolated safety barriers and signal isolators. Selection requires clarifying three elements at once: input signal type (active/passive), output signal type (active/passive), and whether power needs to be supplied to the field device. Common configurations include: passive input → active output (most common), active input → active output (isolator), active input → passive output, and passive input → passive output.
Beijing Pinghe's T Series isolated safety barriers and signal isolators cover all of the configuration types above. Commonly used product models and their selection are compared below:
|
Product Model |
Product Type |
Input/Output Configuration |
Typical Application |
|
PHG-11TD-11-C |
Signal Isolator |
1 in 1 out 4~20mA (HART) input Active 4~20mA (HART) output |
PLC/DCS analog signal isolation transmission; input/output/power three-way isolation |
|
PHD-11TD-21 |
Isolated Safety Barrier (detection end) |
1 in 1 out 2/3-wire transmitter or current source 4~20mA (HART) input Active 4~20mA (HART) output |
Isolated power distribution for hazardous-area 2/3-wire (HART) transmitters; isolates 4~20mA signal from hazardous area to safe area with intrinsically-safe voltage/current limiting; suitable for flammable and explosive locations |
|
PHG-11TE-21M |
Signal Isolator |
1 in 1 out 2/3-wire transmitter or current source 4~20mA (HART) input Active/passive 4~20mA output |
DCS/PLC 4~20mA signal isolation conversion; input/output/power three-way isolation; compatible with active/passive |
|
PHD-22TD-2121 |
Isolated Safety Barrier (detection end) |
2 in 2 out 2/3-wire transmitter or current source 4~20mA (HART) input Active 4~20mA output |
Dual-channel (2 in 2 out) 4~20mA (HART) signal isolation; suitable for multi-loop control systems |
Selection points: clarify the field transmitter type (two-wire/four-wire, active/passive output); confirm the input port type of the receiving device (PLC/DCS); match the corresponding model to the input/output type; and verify that the loop load resistance is within the allowable range. If ground loop interference is present, choose a model with electrical isolation. Beijing Pinghe's PHG Series signal isolators (e.g., PHG-11TD-11-C) use a three-way isolated design for input/output/power, with an isolation voltage of up to 2500V, effectively eliminating ground-loop interference. In flammable and explosive environments, the PHD Series isolated safety barriers (e.g., PHD-11TD-21) limit voltage and current while transmitting the signal, curbing hazardous energy at its source. Smart instruments supporting the HART protocol can use the PHD-12TD-211 (1-in-2-out) or PHD-22TD-2121 (2-in-2-out) HART pass-through models, which provide electrical isolation while passing digital signals through without loss. The full series supports DIN35 rail mounting and has a compact form factor.
VII. Common Issues and Precautions
- Active output mistakenly connected to an active receiving end: the two overlapping power supplies conflict, which may burn out the port; conversion via an isolator is required.
- Passive signal lacking loop power: if a two-wire transmitter is not connected in series with a 24V power supply, it cannot operate and the signal output will be zero.
- Loop load resistance too high: taking a 24V power supply as an example, the maximum load resistance = (24V − 10V) / 20mA = 700Ω; exceeding this will clip the signal.
- Ground loop interference: when the field device and the receiving device are grounded separately, a ground loop forms; a signal isolator with electrical isolation should be used.
VIII. Summary
An active signal is powered by the output device itself, while a passive signal requires an external power supply connected in series in the loop. Correctly distinguishing between the two is the foundation for selection, wiring, and troubleshooting. In practical engineering, a matching isolated safety barrier or signal isolator should be selected based on the field transmitter type and the receiving device's port type, with attention paid to loop load resistance and ground-loop interference issues.
Beijing Pinghe — Making industrial signal connections safer, and automation operation more reliable!